Engine
Cummins 6CTAA8.3-G3 Charge Air Cooled 317 bhp diesel engine. Meets EPA Mobile Off Highway Tier 2, California SCAQMD and CARB permitting requirements. Equipped with filter for crankcase breather and oversized air filter for clean operation in and out of the engine.
Pre-Lubrication System
Engine oil pressure established prior to start-up for longer engine life.
Frequency Control
Woodward electronic speed controller for precise frequency control. Meets HMI lighting requirements.
Controller
Engine control and monitoring, AC monitoring, fault and pre-fault systems are provided by a microprocessor-based controller. All readouts are digital and are listed below. Weatherproof glass cover.
Monitoring
AC Voltage – All Legs
Amperage – All Legs
Frequency – All Legs
Oil Pressure
Water Temperature
Battery Voltage
Fuel Level
Time To Next Service
Faults and Pre-Faults
Oil Pressure Fault/Pre-Fault
Water Temp Fault/Pre-Fault
Over Crank Fault
Over Speed Fault
Low Fuel Fault and Pre-Fault
Low Battery Pre-Fault
Defective Oil Sending Unit Pre-Fault
Defective Water Sending Unit Pre-Fault
Voltage RegulatorPMG Generator
Stamford/Newage UCI 274 H with PMG. Low Wye (120/208) 190KW. Hi Wye (277/480) 196KW ZigZag (120/240) 142KW. PMG provides constant excitation under all conditions. 2/3 pitch windings avoid excessive neutral currents. CSA listed.
MX321 automatic voltage regulator with remote voltage adjustment. Mounted in its own housing with single plug-in connection. Set-up and operating instructions printed on cover. Features include:
- Three Phase Sensing for highly unbalanced
or non-linear loads - Under frequency roll off
- Voltage dip adjustment
- Droop adjustment
- Trim adjustment
Circuit Breaker
2 – 400 amp breakers. One with adjustable amperage for using banded cable without distribution box. Weatherproof glass cover. UL and CSA listed.
Electrical Connection
USA – 18 hole Cam-Lok – E1016 panel includes 4 male grounds, 4 female grounds, 4 neutral, 4 leg one, 4 leg two and 4 leg three. Convenience outlets: two Edison 20A duplex and one 100A Union connector with separate breakers.
CANADA – Cam-Loc 1016 replaced with 400A Ball Nose Connectors, Union connector replaced with 65A Joy connector. UL and CSA listed.
Lifting Devices
- Integrated fork pockets. Allows lifting with forklift
from end of generator - Top mounted lifting hooks allows crane lifting
without damage to generator.
Removable for height reduction.
Optional Accessories
Hi Wye/Low Wye Switch
Change from 120/208 to 277/480 with a flip of a single switch. Includes computerized over current protection and shunt
trips in breakers.
Pow-R-Con Paralleling System with Vacuum Contactor
“The most advanced, comprehensive paralleling solution available today.” Four functions in one
- Display and Programming Panel
- Isochronous Load Sharing
- Auto-Synchronizer
- Load Management
Package includes vacuum contactor and all components for paralleling. Twin-pack and tri-pack configuration accomplished without external common buss.
Remote Annunciator
Remote monitoring of engine and generator via cable.
Operates up to 1700 yards. Includes 50′ cable.
Remote Annunciator with Remote Start
Provides remote monitoring of engine/generator and remote start/stop.
Electronic Service Kit
Provides total redundancy of all electronic parts. Each component plugs in and requires only simple hand tools to install. Includes:
- Woodward Engine Controller
- Magnetic Pick-up
- Engine/Generator Board Set
- Plug-in Voltage Regulator
- Voltage Adjust Pot
Trailer with 200 Gallon Fuel Tank
2 Dexter Torflex axles, 16″ aluminum 5 spoke wheels. E-rated tires, surge hydraulic brakes with LitePOWER Brake Retarder or Electric Brakes, 3 position coupler with your choice of 2-5/16″ ball or drawbar (for Pintle Hook), DOT lighting and markings. 13200 lbs. (6000 kg) GVWR.
Hours of Running Time (200 Gallon Tank)
Load
25%
50%
75%
100%
Time
43:30
25:30
18:00
13:45
WeightDimensions
Generator: L 96″ W 48″ H 84″
Generator, 200 tank, trailer: L 187″ W 96″ H 108″
Will fit inside of common 110″ trailer. Needs no specialized equipment to haul.
Generator (wet-no tank) 7017 lbs. (3190 kg)
Generator, 200 Gallon Tank, LitePOWER
Trailer and 160 Gallons of fuel 9970 lbs. (4532 kg)
Trailer with Secondary Containment Rupture Basin
Same as above with addition of our LitePOWER Integrated Rupture Basin. Large enough to contain all generator fluids including fuel, lube oil and coolant. Sealed from rain water for all weather use.
Noise Level
55 dB(A) @ 50 feet.